RS-485 I/O Modules: ADAM-4000 1-ch Analog Input Module 1-ch RTD Input Module 6-ch RTD Module with Modbus Specifications General Power Consumption 0.7 W @ 24 VDC Supported Protocols ASCII command Connectors 1 x plug-in terminal block (#14 ~ 22 AWG) Analog Input Channels 1 Input Connections 2 or 3-wire Input Impedance 2 MΩ Input Type Pt or Ni RTD RTD Types and Temperature Ranges IEC RTD 100 ohms Pt -100°C to +100°C a = 0.00385 Pt 0°C to +100°C a = 0.00385 Pt 0°C to +200°C a = 0.00385 Pt 0°C to +600°C a = 0.00385 JIS RTD 100 ohms Pt -100°C to +100°C a = 0.003916 Pt 0°C to +100°C a = 0.003916 Pt 0°C to +200°C a = 0.003916 Pt 0°C to +600°C a = 0.003916 Ni RTD Ni -80°C to +100°C Ni 0°C to +100°C Accuracy ±0.1% or better Span Drift ±25 ppm/°C Zero Drift ±3 µV/°C CMR @ 50/60 Hz 150 dB Specifications General Power Consumption 1.2 W @ 24 VDC Supported Protocols ASCII command Connectors 1 x plug-in terminal block (#14 ~ 22 AWG) Analog Input Channels 1 Input Impedance Voltage: 20 MΩ Current: 125 Ω (Added by user) Input Type mV, V or mA Input Range ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V and ±20 mA Accuracy Voltage mode: ±0.1% or better Current mode: ±0.2% or better Span Drift ±25 ppm/°C Zero Drift ±6 µV/°C Digital Input Channels 1 Logic level 0: 1 V max. Logic level 1: 3.5 ~ 30 V pull up current: 0.5 mA, 10 kΩ resistor to 5 V Event Counter Max. input freq.: 50 Hz Min. input pulse width: 1 msec. Digital Output Channels 2, open collector to 30 V, 30 mA max. load Power Dissipation 300 mW ADAM-4012 ADAM-4013 ADAM-4015 Common Specifications General Power Input Unregulated 10 ~ 30 VDC Connectors 1 x plug-in terminal block (#14 ~ 22 AWG) Watchdog Timer System (1.6 second) Analog Input Resolution 16-bit Sampling Rate 10 sample/second (total) NMR @ 50/60 Hz 100 dB Isolation Voltage 3,000 VDC Environment Operating Humidity 5 ~ 95% RH Operating -10 ~ 70°C (14 ~ 158°F) Temperature Storage Temperature -25 ~ 85°C (-13 ~ 185°F) Ordering Information ADAM-4012 1-ch Analog Input Module ADAM-4013 1-ch RTD Input Module ADAM-4015 6-ch RTD Module with Modbus Specifications General Connectors 2 x plug-in terminal blocks (#14 ~ 28 AWG) Power Consumption 1.2 W @ 24 VDC Watchdog Timer System (1.6 s) & Communication Supported Protocols ASCII command and Modbus/RTU Burn-out Detection Yes Analog Input Channels 6 differential Input Connections 2, 3-wire Input Impedance 10 MΩ Input Type Pt, Balco and Ni RTD RTD Types and Temperature Ranges Pt 100 RTD: Pt -50°C to 150°C Pt 0°C to 100°C Pt 0°C to 200°C Pt 0°C to 400°C Pt -200°C to 200°C IEC RTD 100 ohms (a = 0.00385) JIS RTD 100 ohms (a = 0.00392) Pt 1000 RTD Pt -40°C to 160°C Balco 500 RTD -30°C to 120°C Ni 50 RTD Ni -80°C to 100°C Ni 508 RTD Ni 0°C to 100°C BA1 -200°C to 600°C Accuracy ±0.1% (Typical) CMR @ 50/60 Hz 120 dB Span Drift ± 25 ppm/°C Zero Drift ± 3 µV/°C ADAM-4015 RoHS COMPLIANT 2002/95/EC ADAM-4012 ADAM-4013 RoHS COMPLIANT 2002/95/EC RoHS COMPLIANT 2002/95/EC Chapter 16 Table of Contents Table of Contents