70 www.mo xa .c o m Remote I/O > Ethernet I/O Remote Automation Ethernet I/O ioLogik E1210 ioLogik E1211 ioLogik E1212 ioLogik E1214 ioLogik E1213** ioLogik E1240 ioLogik E1241 ioLogik E1242 ioLogik E1260 ioLogik E1262 Input/Output Digital Inputs 16 – 8 6 4 – – 4 – – Digital Outputs – 16 – – 4 – – – – – Relays – – – 6 – – – – – – Configurable DIOs – – 8 – 4 – – 4 – – Analog Inputs – – – – – 8 – 4 – – Analog Outputs – – – – – – 4 – – – RTDs – – – – – – – – 6 – Thermocouples – – – – – – – – – 8 Ethernet Ports (Connector) 2 (RJ45) Speed 10/100 Mbps Switch (Daisy Chain) P P P P P P P P P P Protocols Modbus/TCP (slave), TCP/IP, UDP, DHCP, BOOTP, HTTP, SNMP Environmental Limits Standard Models -10 to 60°C (14 to 140°F) Wide Temp. Models -40 to 75°C (-40 to 167°F) Storage Temperature -40 to 85°C (-40 to 185°F) Operating Humidity 5 to 95% RH (non-condensing) Software Active OPC Server P P P P P P P P P P MX-AOPC UA Server P P P P P P P P P P MXIO P P P P P P P P P P ioSearch P P P P P P P P P P Peer-to-Peer P P P P P P P P – – Standards and Certifications Safety UL 508 EMC EN 55022, EN 55024 EMI CISPR 22, FCC Part 15B Class A EMS EN 61000-4-2; EN 61000-4-3; EN 61000-4-4; EN 61000-4-5; EN 61000-4-6; EN 61000-4-8 Shock IEC 60068-2-27 Vibration IEC 60068-2-6 Hazardous Locations Class 1 Division 2; ATEX Zone 2 Green Product RoHS, CRoHS, WEEE Reliability Warranty 5 years 5 years 5 years 2 years* 5 years 5 years 5 years 5 years 5 years 5 years *Because of the limited lifetime of power relays, products using that component are covered by a 2-year warranty. **DO of ioLogik E1213 is source type